The distribution system indicated below is to be protected with over current protection. Identify the locations where essentially directional over current relays will be required considering proper fault discrimination.
A
Br-2, Br -3, Br -5 and Br -6
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
Br-1, Br -4, Br -7 , Br -5
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
Br-2, Br -3, Br -6
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
Br-1, Br -4, Br -8 and Br -7
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution
The correct option is C Br-2, Br -3, Br -6 Directional relays are not required at supply side and load side because power flow is unidirectional.