Question

The excitation frequency of an LVDT is 2 kHz. The maximum frequency of displacement should be limited to

A
200 Hz
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
1.5 kHz
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
2 kHz
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
2.5 kHz
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is A 200 Hz
For accurate filtering and demodulation of the signal a frequency ratio of 10 : 1 is followed:

Maximum frequency of displacement should be limited to
=2kHz10=200010=200Hz