The HV terminals of a 3-phase bank of three single-phase transformers are connected to a 3-wire, 3-phase 11 kV (line to line) system. The LV terminals are connected to a 3-phase load rated at 1000 kVA and 2200 V line-to-line. When HV is connected in Y and LV in Δ, t he voltage rating of HV winding is ______

A
4.1 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
2.2 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
11 kV
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
6.35 kV
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D 6.35 kV
11 kV,Y/Δ, 2.2 kV, 1000 kVA load
Rating of each transformer =10003=333.3 kVA

VPΔ=2.2 kV

VPY=113=6.35kV