wiz-icon
MyQuestionIcon
MyQuestionIcon
6
You visited us 6 times! Enjoying our articles? Unlock Full Access!
Question

The increment cost curves of three generators are shown, the demand on the system is 240 MW.
For economic load dispatch the generators schedule is





A
P1=20 MW,P2=70 MW,P3=150 MW
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
P1=20 MW,P2=150 MW,P3=70 MW
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
P1=50 MW,P2=50 MW,P3=90 MW
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
P1=20 MW,P2=90 MW,P3=130 MW
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is A P1=20 MW,P2=70 MW,P3=150 MW
G1 is high cost generator, so it will supply minimum power,
P2+P3=220 MW, P1=20 MW
From the curve,(IC210)=0.1(P250)
IC2=0.1×P2+5
For economic dispatch
IC2=IC3
0.1×P2+5=12
P2=70 MW
P3=150 MW

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
ELD Within the Plant Without Transmission Losses
POWER SYSTEMS
Watch in App
Join BYJU'S Learning Program
CrossIcon