The neutral of a 10 MVA, 11 kV alternator is earthed through a resistance of 5 Ω. The earth fault relay is set to operate at 0.75 A. The CT's have a ratio of 1000 : 5. The percentage of alternator winding unprotected is _______%.
11.8
Open in App
Solution
The correct option is A 11.8 Pick up value of relay =1000×0.755=150A
Let the percentage of winding unprotected is xpercent.
Voltage induced in this section, =(11×103√3×x100)