wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

The neutral of a 10 MVA, 11 kV alternator is earthed through a resistance of 5 Ω. The earth fault relay is set to operate at 0.75 A. The CT's have a ratio of 1000 : 5. The percentage of alternator winding unprotected is _______%.
  1. 11.8

Open in App
Solution

The correct option is A 11.8
Pick up value of relay
=1000×0.755=150A
Let the percentage of winding unprotected is x percent.
Voltage induced in this section,
=(11×1033×x100)

150=11×1033×x1005

x=11.80%

flag
Suggest Corrections
thumbs-up
2
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Transformer
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon