Question

The neutral of a 10 MVA, 11 kV alternator is earthed through a resistance of 5 Ω. The earth fault relay is set to operate at 0.75 A. The CT's have a ratio of 1000 : 5. The percentage of alternator winding unprotected is _______%.
  1. 11.8

Open in App
Solution

The correct option is A 11.8
Pick up value of relay
=1000×0.755=150A
Let the percentage of winding unprotected is x percent.
Voltage induced in this section,
=(11×1033×x100)

150=11×1033×x1005

x=11.80%