Question

The power required by a heat pump to maintain a house at 22°C during winter is 3 kW. The rate of heat transfer from the boundary of the house is 4000 kJ/hr per degree temperature difference between inside and outside. The actual COP is 50% of maximum COP. What is the minimum temperature for which the heat pump can meet the heating requirements of the house?

A
1.75°C
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
1.89°C
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
2.04°C
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
2.42°C
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C 2.04°C
(COP)HP=Q1W

W=3 kW

and Q1=4000(T2Tambient)kJ/hr

Q1=40003600(T1Tambient)kW

(COP)HP=40003600×3(T1Tambient)

(COP)max=T1T1Tambient

(COP)HP=0.5×T1T1Tambient

40003600×3(T1Tambient)=0.5T1T1Tambient

1027(T1Tambient)2=0.5×T1

(T1Tambient)2=1.35×T1=1.35×295=398.25

T1Tambient=19.9562

Tambient=29519.9562=275.0438 K=2.0438C