The resistance and leakage reactance of a 10 kVA, 50 Hz, 2300/230 V distribution transformer are:
r1=3.96 Ω,
r2=0.0396 Ω
x1=15.8 Ω,
x2=0.158 Ω
The transformer delivers rated kVA at 0.8 p.f lagging to a load on LV side to maintain 230 V across load terminals. The HV side voltage is _________V.
- 2411.69