Question

The system shown in the figure is supplying 100 MVA at 22 kV, 0.6 lagging power factor into an infinite line

Generator: 200 MVA, 22 kV, X = 0.5 pu
Transformer: 100 MVA, 22/66 kV, X = 0.02 pu
Line Reactance: 10Ω
Choosing the base of 100 MVA, 22 kV, the per unit reactance diagram is

A
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
None of the above
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is B
Generator: 200 MVA, 22 kV,Xd=0.5pu

Xdnew=Xold ×100200×(2222)2

Xdnew=0.5×0.5=0.25 pu

Transformer: 100 MVA, 22/66 kV, X = 0.02 pu

Xnew=0.02 pu

Line Reactance: 10Ω

Xpu=XΩ×MVAbase(kV)2base

=10×100(662)

Xline pu=0.2295 pu

The per unit reactance diagram will be as shown below: