Question

There are two 10 MVA generators of subtransient reactance 15% each and one 5 MVA generator of subtransient reactance 12%. The generators are connected to the station busbars from which load is taken through three 5 MVA, step up transformers each having reactance of 8%. The maximum fault MVA at LV side is _____ MVA.
  1. 175.4

Open in App
Solution

The correct option is A 175.4

Xeqp.u.=(j0.152×j0.24)j0.152+j0.24=j0.057p.u.


Per unit fault MVA is

(MVA)fp.u.=1Xeqp.u.

and fault MVA is (MVA)f=(MVA)bXeqp.u.=100.057=175.4MVA