CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

Two identical 250 kVA, 230/460 V transformers are connected in open delta to supply a balanced 3-ϕ load at 460 V and a power factor of 0.8 lagging. The real power delivered to the load is ______kW.(Assume maximum secondary line current without overloading the transformers).
  1. 346.41

Open in App
Solution

The correct option is A 346.41
The maximum secondary line current without over loading the transformers is,

IL=KVAV=250×103460=543.48 A

In open delta connection,
P1=VI cos (30+ϕ)
P2=VI cos (30ϕ)

Pdelivered=P1+P2=VI[cos(30+ϕ)+cos(30ϕ)]

=2VI cos 30o cos ϕ

=3VLIL cos ϕ

=3×460×543.48×0.8

P=346.41kW

flag
Suggest Corrections
thumbs-up
0
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon