wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

Two identical unloaded generators are connected in parallel as shown below



Both the generators are having positive, negative and zero sequence impedances of 0.6 p.u., 0.4 p.u. and j0.35 p.u. respectively. If prefault voltage is 1 p.u., for a line to ground (L-G) fault at the terminals of the generator, the fault current magnitude in p.u. is______.
(Assume neutral impedance Zn=j0.02p.u.)
  1. 4.36

Open in App
Solution

The correct option is A 4.36
Here both the alternators are working in parallel.



If=3Ia1=3j0.3+j0.2+j0.188=j4.36p.u.

|If|=4.36p.u.

flag
Suggest Corrections
thumbs-up
0
similar_icon
Similar questions
View More
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Transformer
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon