CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
2
You visited us 2 times! Enjoying our articles? Unlock Full Access!
Question

Two similar 400 V, 3-phase alternators share equal kW power delivered to a balanced three phase, 50 kW, 0.8 p.f. lagging load. If the power factor of one machine is 0.9 lag, then the current supplied by other machine is _____A.
  1. 51.47

Open in App
Solution

The correct option is A 51.47
Active power supplied to load = 50 kW

Reactive power supplied to load,
Q=P tan ϕ
=50tan(cos10.8)
=37.5kVAR

Active power supplied by one generator =502=25 kW
Power factor of generator 1 =cosϕ1=0.9 lag

Reactive power supplied by generator 1
=25×tan(cos10.9)=12.10 kVAR

Reactive power supplied by generator 2
=37.512.10
=25.4 kVAR
ϕ2=tan1(25.425)=45.45o
cosϕ2=0.701 lagging


Current supplied by machine 2 is ,

I2=P23 VLcosϕ2=25×1033×400×0.701

=51.47A

flag
Suggest Corrections
thumbs-up
0
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Zener Diode
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon