Two similar 400 V, 3-phase alternators share equal kW power delivered to a balanced three phase, 50 kW, 0.8 p.f. lagging load. If the power factor of one machine is 0.9 lag, then the current supplied by other machine is _____A.
51.47
Open in App
Solution
The correct option is A 51.47 Active power supplied to load = 50 kW
Reactive power supplied to load, Q=Ptanϕ =50tan(cos−10.8) =37.5kVAR
Active power supplied by one generator =502=25kW
Power factor of generator 1 =cosϕ1=0.9lag
Reactive power supplied by generator 1 =25×tan(cos−10.9)=12.10kVAR
Reactive power supplied by generator 2 =37.5−12.10 =25.4kVAR ϕ2=tan−1(25.425)=45.45o
cosϕ2=0.701 lagging