A 10 MVA, 13.8 kV alternator has positive, negative and zero sequence reactances of 30%, 30% and 10% respectively. The value of reactance (in per unit) that should be placed in generator's neutral so that the fault current for a line to ground fault (with zero fault impedance) will not exceed the rated line current is ____ (Asuming system to unloaded prior to fault).