Question

A 10 MVA, 13.8 kV alternator has positive, negative and zero sequence reactances of 30%, 30% and 10% respectively. The value of reactance (in per unit) that should be placed in generator's neutral so that the fault current for a line to ground fault (with zero fault impedance) will not exceed the rated line current is ____ (Asuming system to unloaded prior to fault).

A
0.80
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
0.60
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
0.90
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
0.85
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D 0.85
Given that, X1=X2=0.3p.u
X0=0.1p.u
IF=Ia(rated)=1. p.u
¯¯¯¯Ea=10o
For LG fault, IF=3.EaX1+X2+X0+3Xn+3XfIa
30.3+0.3+0.1+3Xn1 p.u
30.73Xn
Xn2.33=0.766p.u
Xn(min)=0.766p.u
So from Xn>0.766 magnitude of fault current will be less than rated fault current.