A 1500 kVA, 6.6/1.1 kV, 3-ϕ delta-star connection transformer has the following test data,
when low voltage side is short circuited:
300 V, 30 kW, 131.2 A
the per phase reactance referred to delta side is ________Ω.
  1. 3.55

Open in App
Solution

The correct option is A 3.55
Turn ratio for the two winding,

=6.61.13=631

Phase voltage = 300 V

Phase current = 131.23=75.75 A

Power dissipated per phase,

=303=10 kW

(75.75)2Rc1=10×103

Rc1=1.743 Ω

300R2c1+X2c1=75.75

R2c1+X2c1 = 3.96

Xc1=3.556 Ω