A 3-phase induction motor draws 1 MVA at a p.f of 0.8 lag. A synchronous condenser is connected in parallel to draw an additional 750 kVA at 0.6 p.f lead. The p.f of the total load supplied by the mains is _______.
1
Open in App
Solution
The correct option is A 1 The given condition can be explained with phasors,
Active power consumed by induction motor, =1MVA×0.8=800kW
Reactive power consumed by induction motor : =800kW×tan(36.87∘) =600kVAR
Active power consumed by synchronous condenser =450kW×tan(53.13∘) =600kVAR