wiz-icon
MyQuestionIcon
MyQuestionIcon
752
You visited us 752 times! Enjoying our articles? Unlock Full Access!
Question

A 3-phase induction motor draws 1000 kVA at power factor of 0.8 lag. A synchronous condenser is connected in parallel to draw an additional 750 kVA at 0.6 power factor leading. Then the power factor of the total load supplied by the mains is

A
Reactive power absorbed by supply is 600 kVAR.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
Reactive power delivered by supply is 600 kVAR.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
Supply power factor is unity.
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
D
Supply power factor is 0.9 lagging.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is C Supply power factor is unity.
Complex power can be represented as,

¯¯¯¯SIM=1000×0.8+j1000×0.6=800+j600
¯¯¯¯SSC=750×0.6j750×0.8
=450j600

¯¯¯¯STotal=¯¯¯¯SIM+¯¯¯¯SSC
= 800+j600+450j600
¯¯¯¯STotal=1250 kW
Total load supplied by the mains is only real power
pf=1

flag
Suggest Corrections
thumbs-up
3
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Symmetry and Other Circuits
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon