A 3ϕ SC occurs at BUS -4. The SC current flowing between buses 1 and 2 is ___
Assume that the pre fault voltage at all the buses is 1.0 Pu.

Zbus=j⎢ ⎢ ⎢0.150.080.040.070.080.150.060.090.040.060.130.050.070.090.050.12⎥ ⎥ ⎥

A
2.1390o
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
2.1390o
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
C
4.0890o
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
4.0890o
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is B 2.1390o
Before Fault:
V1=1.0, V2=1.0, V3=1.0,V4=1.0 If=I4=V4Z44=1.0j0.12=j8.33

During fault:
V1=IfZ14=I4Z14=0.58V2=IfZ24=I4Z24=0.75

Z14=j0.04
Z24=j0.09

The SC current flowing between buses 1 and 2 is

I12=(V1V2)Z12=(0.580.75)j0.08=2.1390o