A current transformer rated 100/5 A has magnetizing and loss components of the exciting current as 1 A and 0.6 A respectively. The secondary winding burden is purely resistive. It's transformation ratio at rated current is
A
20.12
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
20.20
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
19.88
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
20.00
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution
The correct option is A 20.12 Given, turns ratio of CT,