Question

A single phase ac system comprising of two overhead conductors is to be converted into a 3-phase, 3-wire system by providing an additional conductor of same size. If the operating line voltage, percentage line losses and power factor of load remains same in both systems. The percentage of additional load that can be transmitted by the three phase phase system is

A
86.6%
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
173.2%
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
50%
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
100%
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D 100%
Let the operating voltage and power factor in both the systems be V volts and cos ϕ respectively.

If I1is single phase current, I2 is the three phase current and R is the resistance of each conductor, then
Single phase system:

P1=VI1 cos ϕ Watts
Losses =2I21R Watts

Percentage line losses =W1P1×100=2I21RVI1cos ϕ×100

3-ϕ system
P2=3VI2 cosϕ
Percentage line losses =3I223VI2cos ϕ×100

For the same percentage line losses in both the cases, we have

=2I21RVI1cos ϕ×100=3I223VI2cos ϕ×100

2I1=3I2
I2=23I1

Power transmitted in 3-ϕ system,

P2=3V×23I1cosϕ=2VI1 cos ϕ=2P1

Percentage of additional load =P2P1P1×100

=P1P1×100=100%