Question

An 11000/440 V, 50 Hz, 3-phase transformer is delta connected on the hv side and the lv windings are star connected. There should be 12 V per turn and the flux density is not to exceed 1.2 Wb/m2.
The net cross sectional area of core in cm2 is _______.
  1. 450.45

Open in App
Solution

The correct option is A 450.45
Voltage per turn = 12 V

Vph2N2=12

Also, Vph2N2=4.44×Bm×A×f
12=4.44×1.2×50×A

Area=450.45 cm2