Question

Consider two RCC beams, P and Q each having the section 400 mm x 750 mm (effective depth, d = 750 mm) made with concrete having a τcmax=2.1N/mm2. For the reinforcement provided and the grade of concrete used, it may be assumed that the τc=0.75N/mm2. The design shear in beam P is 400 kN and in beam Q is 750 kN. Considering the provisions of IS : 456-2000, which of the following statements is true?

A
Shear reinforcement should be designed for 175 kN for beam P and the section for beam Q should be revised.
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
Nominal shear reinforcement is required for beam P and the shear reinforcement should be designing for 120 kN for beam Q.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
Shear reinforcement should be designed for 175 kN for beam P and the shear reinforcement should be designed for 525 kN for beam Q.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
The sections for both beams P and Q need to be revised.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is A Shear reinforcement should be designed for 175 kN for beam P and the section for beam Q should be revised.
Beam P
A =400 mm x 700 mm
τcmax=2.1N/mm2
τc=0.75N/mm2
Design shear force,
V = 400 kN
Nominal shear stress

τv=VA=400×100400×750=43

=1.33N/mm2 <τc max

Beam Q
A = 400 mm x 750 mm
τc max=2.1N/mm2
τc=0.75N/mm2
V = 750 kN

τv=VA=750×1000400×750

=2.5N/mm2 >τc max

But τv>τc

So section should be revised.
Shear reinforcement should be provided for shear force

(τvτc)A

=(430.75)×400×750

= 175000N = 175 kN