Question

Consider two RCC beams, Pand Q, each of width 400 mm and effective depth 750 mm, made with concrete having a τcmax=2.0 MPa. For the reinforcement provided and the grade of concrete used, it may be assumed that τc=0.75 MPa. If the design shear for the beams P and Q is 400 kN and 750 kN, respectively, which of the following statements is true considering the provisions of IS 456-2000?

A
Shear reinforcement should be designed for 175 kN for beam P and the section for beam Q should be revised.
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
B
Nominal shear reinforcement is required for beam P and the shear reinforcement should be designed for 120 kN for beam Q.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
Shear reinforcement should be designed for 175 kN for beam P and the section for beam Q should be designed for 525 kN for beam Q.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
The sections for both beams, P and Q, need to be revised.
No worries! We‘ve got your back. Try BYJU‘S free classes today!
Open in App
Solution

The correct option is A Shear reinforcement should be designed for 175 kN for beam P and the section for beam Q should be revised.
Beam P:

Vu=400kN

τv=Vubd=400×103400×750

=1.33N/mm2<τcmax=2.0N/mm2

Vus=(1.330.75)×400×750=175kN

Beam Q:

Vu=750kN

τv=750×103400×750

=2.5N/mm2>τcmax=2.0N/mm2

Not safe, hence section for beam Q should be revised.