For the configuration shown in figure the breaker connecting a large system to bus 2 is initially open. The system 3-phase fault level at bus 3 under this condition is not known. After closing the system breaker, the 3-phase fault level at bus 1 was found to be 5.0 p.u. What will be the new 3-phase fault level at system bus 3 after the interconnection? All per unit values are on common base. Prefault load currents are neglected and prefault voltage are assumed to be 1.0 p.u. at all buses.

Eg = 1.0 p.u., XT = 0.2 p.u., XLine = 0.3 p.u., Xd = 0.2 p.u.
  1. 11.4285

Open in App
Solution

The correct option is A 11.4285

I3ϕ=EfX1

At bus (1),

1=(0.4)(0.3+X)(0.4)+(0.3+X)

EfX1=5pu(given)

or X + 0.7 = 2(0.3 + X)

X = 0.1 pu

Now at bus (3)

X1eq=(0.2+0.2+0.3)×0.1(0.2+0.2+0.3+0.1)=0.7×0.10.8

If=1puXeq=0.80.1×0.7=11.4285pu