Sequence Networks of Transmission Lines, Synchronous Generator, Synchronous Motor
The parameter...
Question
The parameters of transposed overhead transmission line are, Xs=0.8Ω/km andXm=0.2Ω/km. The value of negative sequence reactance X2 and zero sequence reactance X0 respectively will be (inΩ/km)
A
0.3, 0.6
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
0.6, 1.2
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
0.6, 0.9
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
0.3, 1.2
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution
The correct option is D 0.3, 1.2 We know for transposed transmission line,