Question

Three single phase transformers of rating 50 kVA, 2000 V/1000 V are connected in Δ/Δ. The current in the primary windings of the transformer when supplying a balanced three phase load of 40 kW at 1000 V and 0.8 power factor lagging is

A
32.32 A
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
28.86 A
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
16.66 A
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
8.33 A
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D 8.33 A
3VLILcos(ϕ)=40000 W

3×1000×IL×0.8=40000 W

IL=400003×1000×0.8=28.86A

The current in the winding of the transformer secondary,
Iph2=28.863=16.66 A

Current in the primary winding of the transformer,
Iph1=16.66×10002000=8.33 A