An alternator supplying a 600 kW load at 0.75 power factor lagging has its power factor raised to unity by means of over excited synchronous motor. At a constant armature current the reactive power supplied by the motor and the power factor of operation are respectively.

A
529.15 kVAR, zero p.f. lagging
No worries! We‘ve got your back. Try BYJU‘S free classes today!
B
630.23 kVAR, zero p.f. leading
No worries! We‘ve got your back. Try BYJU‘S free classes today!
C
630.23 kVAR, zero p.f. lagging
No worries! We‘ve got your back. Try BYJU‘S free classes today!
D
529.15 kVAR, zero p.f. leading
Right on! Give the BNAT exam to get a 100% scholarship for BYJUS courses
Open in App
Solution

The correct option is D 529.15 kVAR, zero p.f. leading
Given, Load = 600 kW at 0.75 p.f. lagging

Load kVA =6000.75=800kVA

Load kVAR= Load kVA ×sinϕ

=800×1(0.75)2

=529.15 kVAR

When a synchronous motor is connected to improve the power factor, it is over excited. As there is reactive power required from motor so it will operate at zero power factor leading which supplied 529.15 kVAR to load.