CameraIcon
CameraIcon
SearchIcon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

Two 550 kVA alternators operate in parallel to supply the following loads:
(i) 250 kW at 0.6 p.f lagging
(ii) 100 kW at 0.5 p.f. leading
If one machine supply 200 kW at 0.9 p.f lagging, the p.f. of other machine is _____ lagging.
  1. 0.92

Open in App
Solution

The correct option is A 0.92
Real power,

P=PL1+PL2

Q=QL1+QL2

=PL1×tanϕ1+PL2×tanϕ2

Q=250×0.80.6100×321/2=160.128kVAR (lagging)

PG1=200kW

QG1=10.920.9×200×200=96.86kVAR

QG2=160.12896.86=63.26kVAR

PG2=350200=150kW

p.f.=1501502+63.262=0.922lag


flag
Suggest Corrections
thumbs-up
1
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon