wiz-icon
MyQuestionIcon
MyQuestionIcon
1
You visited us 1 times! Enjoying our articles? Unlock Full Access!
Question

Two 800 kVA, 3-phase alternator are operating in parallel and supply a load of 1200 kVA at 0.8 lagging power factor. If one of the machines is operating at 0.9 lagging power factor and supplying 750 kVA, the power factor (lagging) at which the other machine operating is______lagging.
  1. 0.58

Open in App
Solution

The correct option is A 0.58
Sload=1200cos1(0.8)=960j720

SA=750cos1(0.9)=675j326.9

Now, SA+SB=Sload

SB=SloadSA

=960j720675+j326.9

=285j393.1

SB=485.5454.05

cosϕB=cos(54.05)=0.587 (lagging)

flag
Suggest Corrections
thumbs-up
0
Join BYJU'S Learning Program
similar_icon
Related Videos
thumbnail
lock
Symmetry and Other Circuits
PHYSICS
Watch in App
Join BYJU'S Learning Program
CrossIcon